Liquefied Petroleum Gas Cylinder Placement Standard

Liquefied Petroleum Gas Cylinder Placement Standard

Related news 24 12-2020

  The placement of liquefied petroleum gas cylinders is very particular. The invocation of liquefied petroleum gas cylinders stipulated by the state is in accordance with the provisions of DB11/T 450-2007 "Safety Management Requirements for the Use of Bottled LPG in Catering Enterprises". Let TIANLONG Cylinder Factory introduce to you the "Liquefied Petroleum Gas Cylinder Placement Standard":

Liquefied Petroleum Gas Cylinder

  Liquefied petroleum gas cylinders According to Clause 5.2.1: When using liquefied petroleum gas, when the total weight of the cylinder exceeds 1000kg, a separate LPG cylinder room shall be provided. The location between the gas cylinders should be flat and not easy to accumulate liquefied petroleum gas. The fire resistance grade of the building between gas cylinders should not be lower than the requirements of GB 50016-2006, and it should be separated from adjacent buildings by firewall.

  LPG cylinders According to clause 5.2.2: the height between the cylinders should not be less than 2.2m, the ground should be level, and should be higher than the outdoor floor.

  LPG cylinders shall be made of non-sparking materials in accordance with Clause 5.2.3: The ground material between the cylinders shall be used.

  LPG Cylinders According to Clause 5.2.4: The doors and windows between the cylinders shall be opened outwards. There shall be no connecting doors, windows or openings between the cylinder room and the kitchen.

  According to Clause 5.2.5: When natural ventilation is used for LPG cylinders, 2 ventilated shutters shall be set up between cylinders, and the ventilation area per square meter between cylinders shall not be less than 300cm?. The vent should be connected to the outdoor atmosphere, and the distance between the lower edge of the vent should be less than 0.2m from the indoor floor.

  LPG cylinders According to Clause 5.2.6: There shall be no heating channels, floor drains and other underground structures in the cylinder room.

  LPG Cylinder According to Clause 5.2.7: The temperature in the cylinder room shall not exceed 45°C and not lower than 0°C.

  According to Clause 5.2.8: When the total volume of the cylinders in the cylinder room is less than 1m?, the LPG cylinders can be installed in a single-storey dedicated room connected to the outer wall of a building (except for residential, important public buildings and high-rise civil buildings) Inside.

Liquefied Petroleum Gas Cylinder

  Liquefied petroleum gas cylinders According to clause 5.2.9: The cylinder storage for storing gas cylinders shall be set up against the outer wall of the building, and the fire separation distance between the building and the podium shall not be less than 10m. Use and spare cylinders should be placed separately or separated by a firewall. Clear safety warning signs should be set up in the bottle storehouse.

  What I have introduced to you above is "liquefied petroleum gas cylinder placement". TIANLONG LPG Cylinder Factory is a manufacturer specializing in the production of liquefied petroleum gas cylinders. Welcome to call us to discuss business, thank you.

CONTACT

Add:
WIHU Avenue,By ENYO Filling Station Km6,Lagos-Ibadan,express-way,Isheri-Oke,Ogun State,Nigeria

Phone/Whatsapp
+234 906 999 6246

E-mail
mike@tllpg.com

wdh-site
Hangzhou Tianlong Steel Cylinder Co., LtdSupport By Hangzhou Great Master

Follew Us

Contact Us

Contatc Us

wdh-site

Thank you!your cantact letter has been sent!
We will cantact you as soon as possible!

Back
wdh-site

Thank you!your cantact letter has been sent!
We will cantact you as soon as possible!

Back